How Deep Should Geothermal Boreholes Be, and How Far Apart?
A closed loop ground source heat pump for a house usually needs a few hundred metres of drilled pipe in total, split into one or several vertical boreholes. Neighbouring boreholes are normally set several metres apart so they do not drain the same ground. The exact hole depth and spacing come from a heat load calculation and from what the ground can deliver, not from a rule of thumb.
Last updated
What decides geothermal borehole depth?
The ground heat exchanger is the buried part of a closed loop system: the pipe, the fluid and the borehole field around them. The designer sizes it from the heat the house needs on its coldest day and from the heat pump capacity. Software then works out the total bore length, which is the sum of every borehole in the field. Depth per hole is a second decision made after that.
Five inputs matter most:
- Heat load. A larger or leakier home needs more pipe. Cutting heat loss first, as covered in heat pump sizing in cold climates, shortens the loop.
- Thermal conductivity. Rock and wet soil that conduct heat well need less pipe than dry sand or loose gravel.
- Undisturbed ground temperature. Warmer ground at depth helps winter performance. See ground temperature by depth in Canada.
- Groundwater. Moving water carries heat toward the pipe and can reduce the length needed, although it also affects grouting and drilling method.
- Allowed fluid temperatures. The lowest loop fluid temperature the design accepts after several winters limits how hard the ground can be worked.
How is total bore length split into boreholes?
One deep borehole and several shallower ones can supply the same total. The choice depends on drilling conditions and cost more than on heat transfer.
Here is an example with made-up round numbers, not a recommendation. Suppose a design calls for 600 m of total bore length. That could be:
- two boreholes at 300 m, which are uncommon for houses and need a large drilling rig;
- four at 150 m;
- six at 100 m;
- ten at 60 m, which suit shallow bedrock or tight access.
Fewer, deeper holes use less land. More shallow ones can use a smaller rig and reduce the risk of a very deep problem, but they need more pipe connections at the header and more surface area. Drilling depth is also capped in practice by the drilling rig, by how much loose overburden must be cased before the drill reaches bedrock, and by local rules. Some regulators apply extra requirements to boreholes past a stated depth, so the provincial groundwater or environment ministry is the source to check.
Why does borehole spacing matter?
Each borehole draws heat from a column of ground around it. If two holes sit too close, their columns overlap, the soil between them cools through the winter, and the loop fluid returns colder each year. That is thermal interference. It lowers heat pump efficiency slowly, and it is hard to fix once the holes are drilled.
Designers keep boreholes apart so each one has its own share of ground. Design guides often quote a spacing of several metres, commonly in the region of 5 to 8 metres, with deeper boreholes needing more room than shallow ones. Treat that as an often-quoted range and not a rule: the designer should show the simulation behind the number for your site.
Spacing is a trade between land area and drilling length. Where the lot is tight, holes can sit closer if extra pipe is added to compensate. Our guide to geothermal on small lots covers that case. Layout matters too. A borehole in the middle of a grid is surrounded by neighbours and cools faster than one on the edge, so a long line behaves better than a compact block of the same size.
Balanced loads help. A building that also cools in summer pushes heat back into the ground, which recovers some of what winter took out.
How does ground type change the design?
Rock type is one of the biggest swings in a design. Crystalline rock and sandstone conduct heat well. Clay, dry sand and loose till conduct it poorly. Layers differ with depth, so designers use an average over the full depth, weighted by layer thickness.
For houses, designers often use published values for the local geology. For larger fields, a thermal response test is common. The test circulates heated fluid through a trial borehole for a day or two and records how the temperature climbs. The result gives the effective conductivity of the ground and the resistance of the hole itself, which depends on grout, pipe and diameter. A field sized on measured values is less likely to be oversized or undersized.
Grout fills the gap between pipe and rock. It passes heat across that gap and seals the borehole so surface water cannot run down it and separate water layers do not mix. Grout type and sealing method are part of what a licensed driller must follow.
What does the drilling itself involve?
A truck-mounted rig drills each borehole, and the method depends on the ground. Soft overburden is usually cased so the hole does not collapse. In rock the rig drills through with air or water flush. Once drilling is complete, the installer lowers a pre-assembled U-tube of plastic pipe, filled with water, so it does not float or collapse. Then the borehole is grouted from the bottom up. The pipe ends are joined to a horizontal header in trenches that run back to the house, and the whole loop is pressure-tested and flushed before it is filled with heat transfer fluid.
Drilling, grouting and groundwater protection belong to licensed professionals. Rules, permits and approvals vary by province and municipality, and the kind of office to ask is the provincial groundwater or environment ministry and the municipal building and zoning office. Start with geothermal drilling permits in Canada, then see how to choose a geothermal drilling contractor.
Cost follows total metres drilled, the ground, access for the rig and the header work. See geothermal heat pump cost in Canada for the cost drivers. A quote should state the total bore length, the number of boreholes and the depth of each.
How is a heat storage field different?
A borehole field built to store heat follows the opposite logic. At Drake Landing Solar Community in Okotoks, Alberta, 144 boreholes about 35 to 37 m deep were drilled 2.25 m apart across a field about 35 m wide. Close spacing was deliberate. The aim was to warm one block of earth with summer solar heat and take it back in winter, so neighbouring boreholes helped each other hold the heat. That field stored heat. It was not a geothermal heat pump loop. The mechanics are in borehole thermal energy storage and what is a borehole field.
What should you ask a designer or driller?
- What heat load and design day temperature did you use for the home?
- What ground conductivity did you assume, and is it measured or from published data?
- What is the total bore length, the number of holes, the depth of each and the spacing?
- What is the predicted minimum loop fluid temperature after several winters?
- Was a thermal response test done, and who ran it?
- What permits are needed, and who files them?
- How will the boreholes be grouted and sealed, and who certifies the work?
Compare the answers across quotes. The comparison with trench loops is in horizontal vs vertical ground loops.
Quick answers
How deep are geothermal boreholes for a house?
Residential vertical boreholes are commonly quoted from tens of metres to somewhat over a hundred metres each. The designer first finds the total length needed, then splits it into holes that the site and rig can handle.
How far apart should boreholes be?
Design guidance often quotes several metres, roughly 5 to 8 metres, so that boreholes do not draw on the same ground. The right figure depends on depth, ground and load, so ask for the designer's calculation.
Is one deep borehole better than several shallow ones?
Neither is better by default. Deep holes save land and need fewer connections, while shallower holes suit smaller rigs and shallow bedrock. Cost, access and local drilling rules usually decide.
How much total bore length does a house need?
It depends on the heat load, the ground and the heat pump size, so no single figure applies. A designer calculates it from your home's load and the site's ground properties.
Where to verify
Programmes, rules and prices change. Before acting on anything you read here, check it at the source:
- Natural Resources Canada: federal energy-efficiency and clean-energy pages: programme status, EnerGuide labels, technical background.
- Your provincial or territorial energy ministry: current rebates, rules and programme intake dates.
- Provincial regulator for drilling and groundwater: licensing and rules that apply to boreholes and loop fields.
- A licensed professional in your province: sizing, safety and installation for your particular building; these guides are general background only.